INFLA-STOP™ Inflatable Pipe Stopper

Multi-size pneumatic pipe stopper for sealing, blocking and leak testing of pipelines. Reinforced NR/SBR rubber with Kevlar cord, 9 models for pipe bores from 4″ to 72″ (100 – 1,800 mm), working pressure 36 psi (2.5 bar) and back pressure 14.5 psi (1.0 bar).

Additional information

Pipe I.D. range

4″ – 72″ (100 – 1,800 mm)

Working pressure

36 psi (2.5 bar), all models

Back pressure

14.5 psi (1.0 bar), all models

Material

NR/SBR + Kevlar (NBR, CR, EPDM optional)

Air connection

Quick coupling / Schrader

Working temperature

−40 °F to 158 °F (−40 to 70 °C)

Part numbers

210003 – 210017

Pipe I.D.4″ – 72″100 – 1,800 mm · multi-size, 9 models
Working pressure36 psi2.5 bar · all models
Back pressure14.5 psi1.0 bar · all models
MaterialNR/SBR + KevlarNBR, CR, EPDM optional
Air connectionQuick couplingor Schrader valve

INFLA-STOP™ seals off a pipe section so you can control the flow and isolate it for maintenance, leak testing or repair. The body is reinforced rubber with Kevlar cord; it inflates against the pipe wall and blocks the line, then deflates for removal.

Each model covers a wide range of bores, so a few stoppers handle many pipe sizes on site. It is light and quick to deploy through manholes and pipe ends, and it works in sewer, water and industrial lines from −40 °F to 158 °F (−40 to 70 °C).

Key features

  • Reinforced NR/SBR rubber with Kevlar cord
  • NBR for oils, EPDM for chemicals, CR on request
  • Working pressure 36 psi (2.5 bar) and back pressure 14.5 psi (1.0 bar) on every model
  • Quick-coupling or Schrader air connection
  • Eyebolt on top, or top and bottom, to anchor the stopper
  • Multi-size: each model seals a wide bore range, so fewer plugs to carry
  • Light and quick to install and remove
  • Operating temperature −40 °F to 158 °F (−40 to 70 °C)

How to use

Eight steps, one stopper.

  1. Know the stopperThe reinforced rubber body is inflated through its valve and presses on the pipe wall to block the line.
  2. Choose the sizeMeasure the pipe I.D. and pick the model whose range covers it.
  3. Clean the pipeClean the seal area and remove debris and anything sharp that could cut the rubber.
  4. Insert fullyPush the stopper fully inside the pipe, square to the pipe axis.
  5. Inflate with a gaugeInflate slowly through the valve with a calibrated gauge, up to the working pressure of your model.
  6. Fit the restraintAnchor the stopper with a restraint before the line is put under pressure.
  7. Isolate & monitorKeep the back pressure within the limit and watch the gauge. Never stand in line with the stopper.
  8. Release & removeRelease the line pressure first, deflate the stopper fully, then pull it out and inspect it.

Sizes & part numbers

Find your size.

Enter your pipe inner diameter: every model whose range covers it is highlighted. Other sizes on request.

P/N Nominal size Min. pipe Ø Max. pipe Ø Working pressure Back pressure Product Ø Product length Product weight
210003 4–8″100–200 mm 4″100 mm 8″200 mm 36.3 psi2.5 bar 14.5 psi1.0 bar 3.3″85 mm 19.7″500 mm 1 kg
210004 6–12″150–300 mm 6″150 mm 12″300 mm 36.3 psi2.5 bar 14.5 psi1.0 bar 5.3″135 mm 19.7″500 mm 2.2 kg
210005 8–16″200–400 mm 8″200 mm 16″400 mm 36.3 psi2.5 bar 14.5 psi1.0 bar 7.2″182 mm 23.6″600 mm 3.4 kg
210007 12–24″300–600 mm 12″300 mm 24″600 mm 36.3 psi2.5 bar 14.5 psi1.0 bar 11″280 mm 31.5″800 mm 8.1 kg
210008 16–32″400–800 mm 16″400 mm 32″800 mm 36.3 psi2.5 bar 14.5 psi1.0 bar 14″355 mm 39.4″1000 mm 13.7 kg
210009 20–40″500–1000 mm 20″500 mm 40″1000 mm 36.3 psi2.5 bar 14.5 psi1.0 bar 18.9″480 mm 41.3″1050 mm 24.9 kg
210010 24–48″600–1200 mm 24″600 mm 48″1200 mm 36.3 psi2.5 bar 14.5 psi1.0 bar 22.8″580 mm 49.2″1250 mm 36.3 kg
210016 32–64″800–1600 mm 32″800 mm 64″1600 mm 36.3 psi2.5 bar 14.5 psi1.0 bar 30.7″780 mm 78.7″2000 mm 69 kg
210017 48–72″1200–1800 mm 48″1200 mm 72″1800 mm 36.3 psi2.5 bar 14.5 psi1.0 bar — — —

Never exceed the working or back pressure of your model, and never inflate the stopper outside a pipe. Use a calibrated gauge, anchor the stopper before pressurising and never stand in line with it while the line is under pressure. All models: working pressure 36 psi (2.5 bar), back pressure 14.5 psi (1.0 bar).

Applications

Where it works.

Sewer and drain maintenance and testing
Industrial pipelines: flow control and isolation
Water supply networks
Hydrostatic pressure and leak testing
Construction: block open pipe ends against water, dust and debris

My project 0

Need a different size or pressure rating?

Send us the pipe I.D., material and test pressure. We will confirm the right plug and lead time.

Request a quote →